Environmental Meter PCE-HVAC 3
PCE-HVAC 3 is a multifunction environmental meter, tester, or diagnostic meter used for indoor climate and environmental monitoring. In addition to measuring relative humidity and ambient temperature/dry bulb temperature, the meter calculates Celsius (°C) and Fahrenheit (°F), and dew point temperatures. Therefore, heating, ventilation, and air conditioning (HVAC) installations and HVAC system performance evaluations are key applications of the PCE-HVAC 3 meter.
Measurements of relative humidity and ambient temperature / dry bulb temperature are taken directly by built-in sensors. The dew point and wet bulb temperatures are calculated using the readings sent by the sensors of Environmental Meter PCE-HVAC 3.
With a large backlit display and six-button operation, the meter is easy to read and use. The Environmental Meter PCE-HVAC 3 is equipped for one-time on-site measurements as well as for monitoring climate changes over time. The shutdown function can be deactivated for long-term measurements. There is also a thread on the back of the meter to mount the meter on a tripod.
The extreme value measurement function of Environmental Meter PCE-HVAC 3 can be activated during long-term monitoring to determine the minimum or maximum values over a desired period of time.
PCE-HVAC 3 Features
- Ergonomic design
- Large backlit display
- One-handed operation
- Hold and extreme value functions
- Built-in sensors measure relative humidity and ambient room / dry-bulb temperature
- Dew-point temperature and wet-bulb temperature calculation
- The automatic shutdown can be disabled for long-term monitoring
Environmental Meter PCE-HVAC 3 specifications:
- Relative humidity (RH) measuring range 0 … 20% (Accuracy: ± 4% RH)
20 … 40% (Accuracy: ± 3 % RH)
40 … 60% (Accuracy: ± 2% RH)
60 … 80% (Accuracy: ± 3% RH)
80 … 100% (Accuracy: ± 4% RH)
- Ambient room / dry-bulb temperature measuring range -30 … -20°C / -22 … -4°F (Accuracy: ± 1.0°C / 1.8°F)
-20 … 60°C / -4 … 140°F (Accuracy: ± 0.5°C / 0.9°F)
60 … 100°C / 140 … 212°F (Accuracy: ± 1.0°C / 1.8°F)
- Relative humidity resolution 0.1%
- Ambient room / dry-bulb temperature resolution 0.1°C / 0.18°F
- Measuring units Relative humidity (% RH)
- Ambient room / dry-bulb temperature (°C / °F)
- Dew-point temperature (°C / °F)
- Wet-bulb temperature (°C / °F)
- Measuring parameters % RH, GPP (grains per pound), g / kg, g / m³ (absolute), gr / ft³ (absolute)
- Type of sensor Humidity: Precise capacitance
- Temperature: Thermistor
- Absolute humidity 0 … 500 g / m³ 0 … 218.5 gr / ft³
- Dew-point temperature measuring range -30 … 100°C / -22 … 212°F
- Wet-bulb temperature measuring range 0 … 80°C / 32 … 176°F
- Power supply 9V block battery
- Battery life Approx. 48 hours