Three-Phase Power Analyzer PCE-PA 8000
The PCE-PA 8000 is a high-quality three-phase power analyzer designed to accurately measure and analyze electrical parameters in three-phase systems.
The 3-Phase-Power Meter / 3-Phase Power Analyzer is able to measure and record the power in both single-phase or three-phase circuits. With the PCE-PA 8000 3-Phase-Power Meter, you will be able to perform prolonged measurements. Measurement values are saved in xls format on the included SD card of our 3-phase power analyzer to be easily analyzed on the computer.
The measurement sample rate can be set from 2 to 7200 seconds. The pce instruments threephase power analyzer can also measure power and determine both power factor and phase angle. The clamps of the PCE-PA 8000 three-phase power analyzer can be used for cables with a diameter of 50 mm / 2.0 in. The PCE-PA 8000 is the ideal tool to be used in power supply networks. Its 3.7 in / 94 mm display allows you to read all measured values for a quick analysis as well as provide a view of the current, voltage, and power.
To get more information about the PCE-PA 8000 price be in touch with our experts.
- Analysis of a network of 3 phases / 4 conductors, 3 phases / 3 conductors, 1 phase / 2 conductors, 1 phase / 3 conductors
- Measures the effective real value of current and voltage
- Measures active, apparent, and reactive power
- Power Factor (PF), phase angle (Φ)
- Measures voltage up to 600 V
- Measures current up to 1200 A
- It meets the IEC 1010 and CAT III 600 V standards
- Integrated timer and calendar to record data
- Measured values are recorded in the included SD card
- Data is stored in Excel format for further study
- Data can be transferred to a PC through a data cable
- Large 3.7 in / 94 mm LCD display
- Portable electrical power analyzer
Three-Phase Power Analyzer pce pa 8000 Specifications:
- Technical Specifications of pa-8000
Voltage (AC V)
- Measurement range Resolution Accuracy
- 10 V … 600 V (phase to neutral) 0.1 V ±(0.5 % + 0.5 V)
- 10 V … 600 V (phase to neutral)
- Current (AC A)
- 20 A 0.001 A (< 10 A) ±(0.5 % + 0.1 V)
0.01 A (≥ 10 A)
- 200 A 0.01 A (< 100 A) ±(0.5 % + 0.5 A)
0.1 A (≥ 100 A)
- 1200 A 0.1 A (< 1000 A) ±(0.5 A + 5 A)
1 A (≥ 1000 A)
- Active power
- 0 KW … 9.999 KW 0.001 KW ±(1 % + 0.008 KW)
- 10 KW … 99.99 KW 0.01 KW ±(1 % + 0.008 KW)
- 100 KW … 999.9 KW 0.1 KW ±(1 % + 0.8 KW)
- 1 MW … 9.999 MW 0.001 MW ±(1 % + 0.008 MW)
- Apparent power
- 0 KVA … 9.999 KVA 0.001 KVA ±(1 % + 0.008 KVA)
- 10 KVA … 99.99 KVA 0.01 KVA ±(1 % + 0.08 KVA)
- 100 KVA … 999.9 KVA 0.1 KVA ±(1 % + 0.8 KVA)
- 1 MVA … 9.999 MVA 0.001 MVA ±(1 % + 0.008 MVA)