The Kyoritsu KEW 6315 Power Quality Analyzer is one of the best and most efficient tools available on the market for power quality measurement and analysis. With this device, you can get useful information about voltage, current, power, frequency, harmonics, and electrical fluctuations.
One of the outstanding features of this analyzer is its high accuracy in measurement and data analysis. Thanks to its high accuracy, you can detect small changes in power quality and make the necessary decisions to improve it.
Another important feature of the Kyoritsu KEW 6315 Power Quality Analyzer is its ability to remotely monitor and increase the speed and efficiency of the instrument. This feature allows you to review and analyze analyzed data via a PC or Android device.
Considering the reasonable price of the KEW 6315 Electrical Quality Analyzer, this device is suitable for industrial and commercial uses. With it, you can examine energy consumption trends and, if necessary, take steps to improve power quality and reduce energy consumption.
The Kyoritsu KEW 6315 Electrical Quality Analyzer also complies with international standards such as IEC 61010-1 CAT IV 300V, CAT III 600V, and CAT II 1000V, which indicate the quality and reliability of this device.
Overall, the Kyoritsu KEW 6315 Electrical Quality Analyzer is a highly efficient and reliable tool for measuring and analyzing power quality. With this device, you can improve the quality and efficiency of your electrical system and reduce costs. For this reason, it is recommended to purchase the Kyoritsu KEW 6315 power quality analyzer.
Finally, to own one of the best high-precision power quality analyzers, you can purchase a power quality analyzer. Kyoritsu KEW 6315 from our website and enjoy its many features.
To get more information about Kyoritsu kew 6315 price be in touch with our experts.
Electrical connections | 1P2W, 1P3W, 3P3W, 3P4W | |
Metrics and variables | Voltage, Current, Frequency, Active power, Reactive power, Apparent power, Active energy, Reactive energy, Apparent energy, Power factor (cos θ), Neutral current, Demand, Harmonics, Quality (Swell/Dip/Interruption, Transients/Over voltage, Inrush current, Unbalance rate), Capacitance calculation for PF correction unit, Flicker |
|
Voltage (RMS) | ||
Range of product | 600.0 / 1000V | |
Accuracy | 600.0V Range : (sine wave 40 – 70Hz) 10% – 150% against 100V or more of nominal V : Nominal V±0.5% Out of the above range: ±0.2%rdg±0.2%f.s. 1000V Range : ±0.2%rdg±0.2%f.s.(sine wave 40 – 70Hz) |
|
Allowable input | 1 – 120% of each range (rms). 200% of each range (peak) | |
Display range | 0.15 – 130% of each range | |
Crest factor | 3 or less | |
Voltage transient sampling rate | 24µs | |
Current (RMS) | ||
Range | 8128/8135 ( 50A type ) : 5000mA / 50.00A / AUTO 8127 ( 100A type ) : 10.00 / 100.0A / AUTO 8126 ( 200A type ) : 20.00 / 200.0A / AUTO 8125 ( 500A type ) : 50.00 / 500.0A / AUTO 8124/8130 ( 1000A type ) : 100.0 / 1000A / AUTO 8146/8147/8148 ( 10A type ) : 1000mA / 10.00A / AUTO 8133 ( 3000A type ) : 300.0 / 3000A / auto |
|
Accuracy | ±0.2%rdg±0.2%f.s. + accuracy of clamp sensor (sine wave, 40 – 70Hz) | |
Allowable input | 1 – 110% of each range (rms). 200% of each range (peak) | |
Display range of product | 0.15 – 130% of each range | |
Crest factor | 3 or less | |
Active power | ||
Accuracy | ±0.3%rdg±0.2%f.s. + accuracy of clamp sensor (power factor 1, sine wave, 40 – 70Hz) |
|
Influence of power factor | ±1.0%rdg (reading at power factor 0.5 against power factor 1) | |
Frequency meter range | 40 – 70Hz | |
Electric supply (AC Line) | AC100 – 240V / 50 – 60Hz / 7VA max | |
Electric supply (DC battery) | Alcaline size AA battery LR6 or Ni-MH (HR-15-51) × 6 Battery life approx. 3h (LR6, Backlight OFF) |
|
Internal memory | FLASH memory (4MB) | |
PC card interface | SD card (2GB) | |
PC communication interface | USB Ver2.0, Bluetooth Ver2.1 + EDR Class2 | |
Display | 320 × 240 (RGB) Pixel, 3.5inch color TFT display | |
Display update period | 1 sec |
General specifications:
Applicable standards | IEC 61010-1 CAT IV 300V, CAT III 600V, CAT II 1000V Pollution degree 2 IEC 61010-2-030, IEC 61010-031, IEC 61326, EN 50160 IEC 61000-4-30 Class S, IEC 61000-4-15, IEC 61000-4-7 |
Temperature and humidity range | 23±5ºC, less than 85% RH (without condensation) |
Operating temperature & humidity range | 0 – +45ºC, less than 85% RH (without condensation) |
Storage temperature & humidity range | -20 – +60ºC, less than 85% RH (without condensation) |
Power supply (AC Line) | AC100 – 240V / 50 – 60Hz / 7VA max |
Power supply (DC battery) | Alcaline size AA battery LR6 or Ni-MH (HR-15-51) × 6 Battery life approx. 3h (LR6, Backlight OFF) |
Dimensions | 175(L) × 120(W) × 68(D) mm |
Weight | Approx. 900g |
Included Accessories | 7141B (Voltage test lead) 7170 (Power cord) 7219 (USB cable) 8326-02 (SD card 2GB) 9125 (Carrying case for KEW 6315, KEW 6315-01) 9135 (Carrying case for KEW 6315-03, KEW 6315-04, KEW 6315-05) Input terminal plate × 6, KEW Windows for KEW 6315 (PC software), Quick manual, Alkaline size AA battery (LR6) × 6 |
Optional Accessories | 8124/8125/8126/8127/8128 (Load current clamp sensor) 8130/8133(*)/8135(*) (Flexible clamp sensor) 8146/8147/8148 (Leakage and Load current clamp sensor) 8312 (Power supply adaptor) 9132 (Magnet carrying case) |